@WSAR1-V1@:@COMMENT@i-8081 ODM2, 8 Ch. freq. input@DPS@ 2)b[:Us_~O!vpٍ!uTM=Y *kcDumPy& qS`mPy& yR:-K\~_M=Y *kr@q]ͽpٍ!|Y]|UͽpTcDy:@NOTE@zi-8081F2 : 8-channel Frequency input Module. (i-8081-ODM2) *** Target : Target : W-8337/8737 (Wincon ISaGRAF version) Note: 1. Chanel value is integer format in unit of 0.01 Hz , For example, if Ch 1 = 1234, it means frequency is 12.34 Hz 2. Minumum measured frequency 1 Hz , Max is about 1M Hz. If the input frequency is less than 0.96 Hz. the frequency is set as 0. Analog input channel: The first 8 Channel is the frequency of Ch.1 to Ch.8 The last 8 Channel is the "update" of Ch.1 to Ch.8. "update" > 0 means the signal is coming at that PLC scan, so frequency is update to new value. update = 0 means no rising signal(if Active_Type is 1) or no falling signal (if Active_Type is 0) comming at that PLC scan, so frequency is not update. Input type: Isolated or TTL parameters : Input_Type: 0 : Isolated (default) 1 : TTL Active_Type: 0 : Low active 1 : High active (default) TTL_HiLevel: Only for "Input_Type" is set as 1 (TTL). unit is volt TTL_LoLevel: Only for "Input_Type" is set as 1 (TTL). unit is volt ICP DAS , Taiwan Jun.24,2005 @PARAM@#A+I[1,16]0205 #AH:ref,8081F2 #LA:Input_Type,0 #LA:Active_Type,1 #LH:TimeTick_Level,3 #LH:reserved,0 #LH:reserved,0 #LH:reserved,0 #LH:reserved,0 #LH:reserved,0 #FA:TTL_HiLevel,2.4 #FA:TTL_LoLevel,0.8 @END@